NSF Product and Service Listings

These NSF Official Listings are current as of Wednesday, July 2, 2025 at 12:15 a.m. Eastern Time. Please contact NSF to confirm the status of any Listing, report errors, or make suggestions.

Alert: NSF is concerned about fraudulent downloading and manipulation of website text. Always confirm this information by clicking on the below link for the most accurate information: http://info.nsf.org/Certified/PwsChemicals/Listings.asp?Company=0T110&Standard=060&


NSF/ANSI/CAN 60
Drinking Water Treatment Chemicals - Health Effects



 
Anchem Sales 
120 Stronach Crescent
London, ON N5V 3A1 
Canada 
800-387-9799 
519-451-1614
Visit this company's website

Facility : London, Ontario, Canada


Aluminum Sulfate[AL]
Trade Designation Product Function Max Use
Aluminum Sulphate 48% Coagulation & Flocculation 150mg/L

[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
     drinking water shall not exceed 2 mg/L.

Hydrochloric Acid
Trade Designation Product Function Max Use
Hydrochloric Acid 20 BE (32%) Corrosion & Scale Control
pH Adjustment
45mg/L
OXYNET Corrosion & Scale Control
pH Adjustment
135mg/L

Hydrogen Peroxide[HP]
Trade Designation Product Function Max Use
Anprox 10 Oxidant 10.5mg/L
Anprox 25 Oxidant 4.2mg/L
Anprox 35 Oxidant 3mg/L
Anprox 50 Oxidant 2.1mg/L
OXYNET - X Oxidant 3mg/L

[HP] Use of this product shall be followed by chlorination to remove levels of hydrogen
     peroxide.  Chlorine residuals shall not exceed 4 mg/L, the EPA's proposed maximum
     residual level.

Polyaluminum Chloride[AL]
Trade Designation Product Function Max Use
Poly Aluminum Chloride Coagulation & Flocculation 250mg/L

[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
     drinking water shall not exceed 2 mg/L.

Sodium Bisulfite[1]
Trade Designation Product Function Max Use
Sodium Bisulphite 38% Dechlorinator & Antioxidant 50mg/L

[1] This product contains sulfite.
    Sulfites have been known to cause potentially lethal allergic reactions in sulfite-sensitive individuals.
    The maximum recommended allowable residual sulfite level in the finished drinking water is 100 ppb (0.1 mg/L).

Sodium Hydroxide
Trade Designation Product Function Max Use
Caustic Soda 25% pH Adjustment 200mg/L
Caustic Soda 30% pH Adjustment 167mg/L
Caustic Soda 50% pH Adjustment 100mg/L

Sodium Hypochlorite[HY]
Trade Designation Product Function Max Use
Anchlor 12 Disinfection & Oxidation 60mg/L
Anchlor 15 Disinfection & Oxidation 51mg/L
Anchlor 19 Disinfection & Oxidation 59mg/L
Anchlor 6 Disinfection & Oxidation 109mg/L

[HY] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
     dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
     finished drinking water to ensure compliance to all applicable regulations. Also,
     reference the AWWA B300 (Hypochlorites) standard's Recommendations for the Handling and
     Storage of Hypochlorite Solutions appendix for information on preservation techniques
     for hypochlorite bleach in transit and storage.

Sodium Silicate
Trade Designation Product Function Max Use
Sodium Silicate Corrosion & Scale Control 42mg/L

Sulfuric Acid
Trade Designation Product Function Max Use
Sulphuric Acid 50% Corrosion & Scale Control
pH Adjustment
100mg/L
Sulphuric Acid 93% Corrosion & Scale Control
pH Adjustment
50mg/L


Number of matching Manufacturers is 1
Number of matching Products is 20
Processing time was 0 seconds