NSF/ANSI/CAN 60
Drinking Water Treatment Chemicals - Health Effects



 
American Development Corporation 
821 William D. Jones Boulevard
P.O. Box 620 
Fayetteville, TN 37334 
United States 
888-542-8561 
931-438-0653
Visit this company's website

Facility : Fayetteville, TN


Aluminum Chloride[AL]
Trade Designation Product Function Max Use
ADC-9660 Coagulation & Flocculation 70mg/L
EC-800 Coagulation & Flocculation 70mg/L

[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
     drinking water shall not exceed 2 mg/L.

Aluminum Chlorohydrate[AL]
Trade Designation Product Function Max Use
ADC-9612 Coagulation & Flocculation 175mg/L
ADC-9613 Coagulation & Flocculation 250mg/L
ADC-9630 Coagulation & Flocculation 250mg/L
EC-309 Coagulation & Flocculation 175mg/L
EC-309HB Coagulation & Flocculation 250mg/L
EC-409 Coagulation & Flocculation 250mg/L
EC-413 Coagulation & Flocculation 250mg/L

[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
     drinking water shall not exceed 2 mg/L.

Aluminum Sulfate[AL]
Trade Designation Product Function Max Use
Alum Coagulation & Flocculation 150mg/L
Aluminum Sulfate Coagulation & Flocculation 150mg/L

[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
     drinking water shall not exceed 2 mg/L.

Blended Coagulation Chemicals[AL]
Trade Designation Product Function Max Use
EC-609 Coagulation & Flocculation 272mg/L

[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
     drinking water shall not exceed 2 mg/L.

Blended Phosphates
Trade Designation Product Function Max Use
AmPhos 37 Corrosion & Scale Control 23mg/L
AmPhos 55 Corrosion & Scale Control 23mg/L
Aqua Mag Corrosion & Scale Control 23mg/L
CARUS™ 8600 Corrosion & Scale Control
Sequestering
18mg/L
Carus 8500 Corrosion & Scale Control 18mg/L
F-35 Corrosion & Scale Control 18mg/L
K-5 Corrosion & Scale Control 23mg/L

Calcium Thiosulfate
Trade Designation Product Function Max Use
Captor[1] Dechlorination
Ozone Reduction
50mg/L

[1] This product is to be used for the destruction of residual chlorine. It should be
    applied only to the extent necessary to ensure chlorine removal. Actual chlorine
    concentration in the water should be used to calculate the necessary dose of calcium
    thiosulfate.

Citric Acid[2] [3]
Trade Designation Product Function Max Use
Citric Acid 50% Solution Membrane Cleaner NA

[2] This product is designed to be used off-line and flushed out prior to using the system
    for drinking water, following manufacturer's use instructions.
[3] The pH of the influent and effluent water should be monitored to ensure that all traces
    of the product have been removed before placing into service.

Dipotassium Orthophosphate
Trade Designation Product Function Max Use
CARUS™ 4200 Corrosion & Scale Control 27mg/L

Ferric Chloride
Trade Designation Product Function Max Use
Ferric Chloride Liquid 38-42% Coagulation & Flocculation 250mg/L

Ferric Sulfate
Trade Designation Product Function Max Use
CPR-4245 Coagulation & Flocculation 500mg/L
FerriClear Coagulation & Flocculation 500mg/L
Ferric Sulfate Coagulation & Flocculation 500mg/L

Fluosilicic Acid
Trade Designation Product Function Max Use
Fluosilicic Acid Fluoridation 6mg/L
HFS Acid Fluoridation 6mg/L
Hydrofluosilicic Acid Fluoridation 6mg/L

Hydrochloric Acid
Trade Designation Product Function Max Use
Hydrochloric Acid 28% Corrosion & Scale Control
pH Adjustment
50mg/L
Hydrochloric Acid 32% Corrosion & Scale Control
pH Adjustment
44mg/L

Hydrogen Peroxide[HP]
Trade Designation Product Function Max Use
Hydrogen Peroxide 10% Oxidant
Dechlorination
10mg/L
Hydrogen Peroxide 25% Oxidant
Dechlorination
3.8mg/L
Hydrogen Peroxide 27.5% Oxidant
Dechlorination
3.8mg/L
Hydrogen Peroxide 30% Oxidant
Dechlorination
3.5mg/L
Hydrogen Peroxide 8% Oxidant
Dechlorination
13mg/L

[HP] Use of this product shall be followed by chlorination to remove levels of hydrogen
     peroxide.  Chlorine residuals shall not exceed 4 mg/L, the EPA's proposed maximum
     residual level.

Miscellaneous Treatment Applications[CP]
Trade Designation Product Function Max Use
Earth tec Algicide
Bactericide
Molluscicide
19mg/L
EarthTec® Algicide
Bactericide
Molluscicide
19mg/L

[CP] The finished drinking water shall be monitored to ensure that levels of copper do

     not exceed 1.3 mg/L.

Phosphoric Acid
Trade Designation Product Function Max Use
CARUS™ 4105 Corrosion & Scale Control 17mg/L
Quantichem-Ortho Corrosion & Scale Control 17mg/L

Poly (Diallyldimethylammonium Chloride)(pDADMAC)
Trade Designation Product Function Max Use
CPO-4120 Coagulation & Flocculation 45mg/L

Polyaluminum Chloride [AL]
Trade Designation Product Function Max Use
ACH[4] Coagulation & Flocculation 250mg/L
ADC-9601 Coagulation & Flocculation 403mg/L
ADC-9610 Coagulation & Flocculation 175mg/L
ADC-9611 Coagulation & Flocculation 250mg/L
ADC-9612 Coagulation & Flocculation 175mg/L
ADC-9630 Coagulation & Flocculation 250mg/L
Aluminum Chlorohydrate[4] Coagulation & Flocculation 250mg/L
EC-209HB Coagulation & Flocculation 403mg/L
EC-300[4] Coagulation & Flocculation 100mg/L
EC-300HB Coagulation & Flocculation 250mg/L
EC-309 Coagulation & Flocculation 175mg/L
EC-309HB Coagulation & Flocculation 250mg/L
EC-409 Coagulation & Flocculation 250mg/L
EC-413 Coagulation & Flocculation 250mg/L
PAC[4] Coagulation & Flocculation 250mg/L
Polyaluminum Chloride[4] Coagulation & Flocculation 250mg/L

[4] This product contains sulfite. Sulfites have been known to cause potentially lethal
    allergic reactions in sulfite-sensitve individuals. The maximum recommended allowable
    residual sulfite level in the finished drinking water is 100 ppb (0.1 mg/L).
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
     drinking water shall not exceed 2 mg/L.

Polyaluminum Chlorosulfate[AL]
Trade Designation Product Function Max Use
ADC-9614 Coagulation & Flocculation 200mg/L
EC-309S Coagulation & Flocculation 200mg/L

[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
     drinking water shall not exceed 2 mg/L.

Polymer Blends[AL] [PY]
Trade Designation Product Function Max Use
ADC-801 Coagulation & Flocculation 250mg/L
ADC-812 Coagulation & Flocculation 181mg/L
ADC-9610 Coagulation & Flocculation 175mg/L
ADC-9611 Coagulation & Flocculation 250mg/L
ADC-9612 Coagulation & Flocculation 143mg/L
ADC-9613 Coagulation & Flocculation 250mg/L
ADC-9614 Coagulation & Flocculation 143mg/L
ADC-9615 Coagulation & Flocculation 206mg/L
ADC-9631 Coagulation & Flocculation 32mg/L
ADC-9632 Coagulation & Flocculation 100mg/L
ADC-9633 Coagulation & Flocculation 185mg/L
Delta-Floc 801 Coagulation & Flocculation 250mg/L
Delta-Floc 812 Coagulation & Flocculation 181mg/L
EC-265 Coagulation & Flocculation 211mg/L
EC-369 Coagulation & Flocculation 206mg/L
EC-461 Coagulation & Flocculation 32mg/L
EC-473 Coagulation & Flocculation 100mg/L
EC-475 Coagulation & Flocculation 185mg/L
EC-675 Coagulation & Flocculation 275mg/L

[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
     drinking water shall not exceed 2 mg/L.
[PY] Polyamines Certified by NSF International comply with 40 CFR 141.111 requirements for
     percent monomer and dose.

Sodium Hydroxide
Trade Designation Product Function Max Use
25% Caustic Soda pH Adjustment 100mg/L
40% Caustic Soda pH Adjustment 100mg/L
50% Caustic Soda pH Adjustment 100mg/L
Caustic pH Adjustment 100mg/L
Caustic Soda pH Adjustment 100mg/L
Caustic Soda Solution, 30% Corrosion & Scale Control
pH Adjustment
167mg/L
Lye pH Adjustment 100mg/L
Sodium Hydrate pH Adjustment 100mg/L
Sodium Hydroxide, 25% pH Adjustment 100mg/L
Sodium Hydroxide, 40% pH Adjustment 100mg/L
Sodium Hydroxide, 50% pH Adjustment 100mg/L

Sodium Hypochlorite[CL]
Trade Designation Product Function Max Use
Bleach Disinfection & Oxidation 84mg/L
Sodium Hypochlorite Disinfection & Oxidation 84mg/L

[CL] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
     dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
     finished drinking water to ensure compliance to all applicable regulations.

Sodium Permanganate[PO]
Trade Designation Product Function Max Use
CARUSOL®-20 Disinfection & Oxidation 176mg/L
Sodium Permanganate, 20% Disinfection & Oxidation 176mg/L

[PO] The finished drinking water shall be monitored to ensure that levels of manganese

     do not exceed 0.05 mg/L.

Sodium Polyphosphates, Glassy
Trade Designation Product Function Max Use
CARUS™ 1100 Corrosion & Scale Control
Sequestering
22mg/L

Sulfuric Acid
Trade Designation Product Function Max Use
Sulfuric Acid 93% Corrosion & Scale Control
pH Adjustment
50mg/L

Zinc Orthophosphate[5]
Trade Designation Product Function Max Use
CARUS™ 3180 Corrosion & Scale Control 16mg/L

[5] Based on an evaluation of health effects data, the level of zinc in the finished
    drinking water should not exceed 2.0 mg/L.