NSF Product and Service Listings

These NSF Official Listings are current as of Saturday, November 21, 2026 at 12:15 a.m. Eastern Time. Please contact NSF to confirm the status of any Listing, report errors, or make suggestions.

Alert: NSF is concerned about fraudulent downloading and manipulation of website text. Always confirm this information by clicking on the below link for the most accurate information: http://info.nsf.org/Certified/PwsComponents/Listings.asp?Company=C0703132&Standard=061&



NSF/ANSI/CAN 61
Drinking Water System Components - Health Effects

NOTE: Unless otherwise indicated for Materials, Certification is only for the Water Contact Material shown in the Listing. Click here for a list of Abbreviations used in these Listings. Click here for the definitions of Water Contact Temperatures denoted in these Listings. Products certified to NSF/ANSI/CAN 61 comply with the health effects criteria in NSF/ANSI/CAN 600.


 
Henkel Corporation 
1 Henkel Way
Rocky Hill, CT 06067 
United States 
855-708-3617
Visit this company's website


Facility : Houston, TX

Protective (Barrier) Materials

    Water Water
  Water Contact Contact Contact
Trade Designation Size Restriction Temp Material

Coatings - Fittings [G]
LOCTITE® RenewWrap DWF[1] [2] >= 6" CLD 23 EPOXY
LOCTITE® Tyfo® PWC[1] [2] >= 6" CLD 23 EPOXY

[1] Number of Coats: 2
    Maximum Field Use Dry Film Thickness (in mils): 19
    Maximum Thinner: None
    Recoat Cure Time and Temperature: 24 hours at 72°F
    Final Cure Time and Temperature: 24 hours at 72°F
    Special Comments: Mix ratio A:B is 100:32.4 by weight.
[2] Only products bearing the NSF mark are NSF Certified.
[G] Product is Certified to NSF/ANSI/CAN 372 and conforms with the lead content requirements
    for "lead free" plumbing as defined by California, Vermont, Maryland, and Louisiana
    state laws and the U.S. Safe Drinking Water Act.

Coatings - Pipe [G]
LOCTITE® RenewWrap DWF[1] [2] >= 14" CLD 23 EPOXY
LOCTITE® RenewWrap System[2] [3] >= 36" CLD 23 EPOXY
LOCTITE® Tyfo® PWC[1] [2] >= 14" CLD 23 EPOXY
LOCTITE® Tyfo® System[2] [4] >= 36" CLD 23 EPOXY

[1] Number of Coats: 2
    Maximum Field Use Dry Film Thickness (in mils): 19
    Maximum Thinner: None
    Recoat Cure Time and Temperature: 24 hours at 72°F
    Final Cure Time and Temperature: 24 hours at 72°F
    Special Comments: Mix ratio A:B is 100:32.4 by weight.
[2] Only products bearing the NSF mark are NSF Certified.
[3] LOCTITE® RenewWrap System Product Application:
    			
    Layer 1: 10 wet mils of LOCTITE® RenewWrap XPL. This layer must cure for 1 hour at 75°F.
    Mix ratio of LOCTITE® RenewWrap XPL. Part A:B is 100:34.5 by weight.
    
    Layer 2: 40 wet mils of LOCTITE® RenewWrap XPL or thickened LOCTITE® RenewWrap XPL. No
    cure time required. Mix ratio of LOCTITE® RenewWrap XPL Part A:B is 100:34.5 by weight.
    Thickened LOCTITE® RenewWrap XPL is mixed as (Mixed LOCTITE® RenewWrap XPL Epoxy) :
    (Filler material) 100:7 Parts by weight. Filler material may be a combination of fumed
    silica or polyethylene fibers.
    
    Layer 3: 8 coats of the reinforcement Layer saturated with LOCTITE® RenewWrap XPL. This
    layer must cure for 3 hours at 75F. Mix ratio of Part A:B is 100:34.5 by weight.
    Reinforcement layer may be a combination of LOCTITE® RenewWrap CF700, LOCTITE® RenewWrap
    CF1500, LOCTITE® RenewWrap GF1100, LOCTITE® RenewWrap CF650-BX (carbon) GF2200 (glass),
    LOCTITE® RenewWrap GF-WP (glass), LOCTITE® RenewWrap GF800-BX (glass), and LOCTITE®
    RenewWrap GF750 (glass). 
    
    Layer 4: 20 wet mils of Thickened LOCTITE® RenewWrap XPL. Final cure is 48 hours at
    80°F. Minimum Shore D hardness of 80. Mix ratio of LOCTITE® RenewWrap XPL Part A:B is
    100:34.5 by weight, then (Mixed Epoxy) : (Filler material) 100:7 Parts by weight. If 80
    hardness is not achieved, continue curing in 3 hour intervals. Hardness shall be based
    on average of 5 measurements. Filler material may be a combination of fumed silica or
    polyethylene fibers. 
    							
    Alternate Part 4: 2 coats (13 wet mils each) of LOCTITE® RenewWrap DWF. First coat must
    cure for 24 hours at 75°F prior to the application of the second coat. Final cure is 24
    hours at 72°F. Mix ratio of Part A:B is 100:32.4 by weight.
[4] LOCTITE® Tyfo System Product Application:
    Layer 1: 10 wet mils of Tyfo S. This layer must cure for 1 hour at 75°F.  Mix ratio of
    Tyfo S Part A:B is 100:34.5 by weight.
    
    Layer 2: 40 wet mils of Tyfo TC, Tyfo S or thickened Tyfo S.  No cure time required. 
    Mix ratio of Tyfo TC Part A:B is 100:23.4 by weight.  Mix ratio of Tyfo S Part A:B is
    100:34.5 by weight. Thickened Tyfo S is mixed as (Mixed Tyfo S Epoxy) : (Filler
    Material) 100:7 Parts by weight. Filler Material may be a combination of fumed silica or
    polyethylene fibers.
    
    Layer 3: 8 coats of the reinforcement Layer saturated with Tyfo S. This layer must cure
    for 3 hours at 75F. Mix ratio of Part A:B is 100:34.5 by weight.  Reinforcement layer
    may be a combination of Tyfo SCH-41, Tyfo SCH-41 2X, Tyfo SEH-51A, Tyfo BCC (carbon)
    SEH-81A (glass), Tyfo WEB (glass),Tyfo BC (glass), Tyfo SEH-31A (glass), Tyfo SEH-31A
    (glass), Tyfo SCH-41S (carbon) and Tyfo SCH-41S-2X (carbon).
    
    Layer 4: 20 wet mils of Thickened Tyfo S. Final cure is 48 hours at 80°F. Minimum Shore
    D hardness of 80. Mix ratio of Tyfo S Part A:B is 100:34.5 by weight, then (Mixed Epoxy)
    : (Filler Material) 100:7 Parts by weight. If 80 hardness is not achieved, continue
    curing in 3 hour intervals.  Hardness shall be based on average of 5 measurements. 
    Filler material may be a combination of fumed silica or polyethylene fibers.
    
    Alternate Part 4: 2 coats (13 we mils each) of Tyfo PWC. First coat must cure for 24
    hours at 75°F prior to the application of the second coat.  Final cure is 24 hours at
    72°F.  Mix ratio of Part A:B is 100:32.4 by weight.
[G] Product is Certified to NSF/ANSI/CAN 372 and conforms with the lead content requirements
    for "lead free" plumbing as defined by California, Vermont, Maryland, and Louisiana
    state laws and the U.S. Safe Drinking Water Act.

Coatings - Tank [G]
LOCTITE® RenewWrap DWF[1] [2] >= 500 gal. CLD 23 EPOXY
LOCTITE® RenewWrap System[2] [3] >= 2000 gal. CLD 23 EPOXY
LOCTITE® Tyfo® PWC[1] [2] >= 500 gal. CLD 23 EPOXY
LOCTITE® Tyfo® System[2] [4] >= 2000 gal. CLD 23 EPOXY

[1] Number of Coats: 2
    Maximum Field Use Dry Film Thickness (in mils): 19
    Maximum Thinner: None
    Recoat Cure Time and Temperature: 24 hours at 72°F
    Final Cure Time and Temperature: 24 hours at 72°F
    Special Comments: Mix ratio A:B is 100:32.4 by weight.
[2] Only products bearing the NSF mark are NSF Certified.
[3] LOCTITE® RenewWrap System Product Application:
    			
    Layer 1: 10 wet mils of LOCTITE® RenewWrap XPL. This layer must cure for 1 hour at 75°F.
    Mix ratio of LOCTITE® RenewWrap XPL. Part A:B is 100:34.5 by weight.
    
    Layer 2: 40 wet mils of LOCTITE® RenewWrap XPL or thickened LOCTITE® RenewWrap XPL. No
    cure time required. Mix ratio of LOCTITE® RenewWrap XPL Part A:B is 100:34.5 by weight.
    Thickened LOCTITE® RenewWrap XPL is mixed as (Mixed LOCTITE® RenewWrap XPL Epoxy) :
    (Filler material) 100:7 Parts by weight. Filler material may be a combination of fumed
    silica or polyethylene fibers.
    
    Layer 3: 8 coats of the reinforcement Layer saturated with LOCTITE® RenewWrap XPL. This
    layer must cure for 3 hours at 75F. Mix ratio of Part A:B is 100:34.5 by weight.
    Reinforcement layer may be a combination of LOCTITE® RenewWrap CF700, LOCTITE® RenewWrap
    CF1500, LOCTITE® RenewWrap GF1100, LOCTITE® RenewWrap CF650-BX (carbon) GF2200 (glass),
    LOCTITE® RenewWrap GF-WP (glass), LOCTITE® RenewWrap GF800-BX (glass), and LOCTITE®
    RenewWrap GF750 (glass). 
    
    Layer 4: 20 wet mils of Thickened LOCTITE® RenewWrap XPL. Final cure is 48 hours at
    80°F. Minimum Shore D hardness of 80. Mix ratio of LOCTITE® RenewWrap XPL Part A:B is
    100:34.5 by weight, then (Mixed Epoxy) : (Filler material) 100:7 Parts by weight. If 80
    hardness is not achieved, continue curing in 3 hour intervals. Hardness shall be based
    on average of 5 measurements. Filler material may be a combination of fumed silica or
    polyethylene fibers. 
    							
    Alternate Part 4: 2 coats (13 wet mils each) of LOCTITE® RenewWrap DWF. First coat must
    cure for 24 hours at 75°F prior to the application of the second coat. Final cure is 24
    hours at 72°F. Mix ratio of Part A:B is 100:32.4 by weight.
[4] LOCTITE® Tyfo System Product Application:
    Layer 1: 10 wet mils of Tyfo S. This layer must cure for 1 hour at 75°F.  Mix ratio of
    Tyfo S Part A:B is 100:34.5 by weight.
    
    Layer 2: 40 wet mils of Tyfo TC, Tyfo S or thickened Tyfo S.  No cure time required. 
    Mix ratio of Tyfo TC Part A:B is 100:23.4 by weight.  Mix ratio of Tyfo S Part A:B is
    100:34.5 by weight. Thickened Tyfo S is mixed as (Mixed Tyfo S Epoxy) : (Filler
    Material) 100:7 Parts by weight. Filler Material may be a combination of fumed silica or
    polyethylene fibers.
    
    Layer 3: 8 coats of the reinforcement Layer saturated with Tyfo S. This layer must cure
    for 3 hours at 75F. Mix ratio of Part A:B is 100:34.5 by weight.  Reinforcement layer
    may be a combination of Tyfo SCH-41, Tyfo SCH-41 2X, Tyfo SEH-51A, Tyfo BCC (carbon)
    SEH-81A (glass), Tyfo WEB (glass),Tyfo BC (glass), Tyfo SEH-31A (glass), Tyfo SEH-31A
    (glass), Tyfo SCH-41S (carbon) and Tyfo SCH-41S-2X (carbon).
    
    Layer 4: 20 wet mils of Thickened Tyfo S. Final cure is 48 hours at 80°F. Minimum Shore
    D hardness of 80. Mix ratio of Tyfo S Part A:B is 100:34.5 by weight, then (Mixed Epoxy)
    : (Filler Material) 100:7 Parts by weight. If 80 hardness is not achieved, continue
    curing in 3 hour intervals.  Hardness shall be based on average of 5 measurements. 
    Filler material may be a combination of fumed silica or polyethylene fibers.
    
    Alternate Part 4: 2 coats (13 we mils each) of Tyfo PWC. First coat must cure for 24
    hours at 75°F prior to the application of the second coat.  Final cure is 24 hours at
    72°F.  Mix ratio of Part A:B is 100:32.4 by weight.
[G] Product is Certified to NSF/ANSI/CAN 372 and conforms with the lead content requirements
    for "lead free" plumbing as defined by California, Vermont, Maryland, and Louisiana
    state laws and the U.S. Safe Drinking Water Act.


Number of matching Manufacturers is 1
Number of matching Products is 10
Processing time was 0 seconds