NSF/ANSI/CAN 60
Drinking Water Treatment Chemicals - Health Effects
Drinking Water Treatment Chemicals - Health Effects
| Garratt-Callahan Company | |
| 50 Ingold Drive | |
| Burlingame, CA 94010-2206 | |
| United States | |
| 650-697-5811 | |
| Visit this company's website |
Facility : Burlingame, CA
|
Aluminum Chlorohydrate[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7032 | Coagulation & Flocculation | 250mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
|
||
|
Blended Corrosion Inhibitor |
||
| Trade Designation | Product Function | Max Use |
| Formula 647 | Corrosion & Scale Control Sequestering |
27mg/L |
|
Blended Phosphates |
||
| Trade Designation | Product Function | Max Use |
| Formula 6648 | Corrosion & Scale Control Sequestering |
50mg/L |
|
Chlorine Dioxide, Liquid[CL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 3080 | Disinfection & Oxidation | 670mg/L |
[CL] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations.
|
||
|
Hydrochloric Acid[1] |
||
| Trade Designation | Product Function | Max Use |
| Formula 5300 | Other | 40mg/L |
| Formula 5307 | Other | 40mg/L |
[1] Certified for use as an activator for sodium chlorite in the generation of chlorine
dioxide.
|
||
|
Miscellaneous Corrosion Chemicals |
||
| Trade Designation | Product Function | Max Use |
| Formula 153 | Corrosion & Scale Control Sequestering |
50mg/L |
|
Miscellaneous Treatment Chemical[2] |
||
| Trade Designation | Product Function | Max Use |
| Formula 65 | Antifoamer | 50mg/L |
[2] Certified for addition to the feedwater for evaporate desalination units only. |
||
|
Miscellaneous Water Supply Products |
||
| Trade Designation | Product Function | Max Use |
| Formula 3010[3] | Reverse Osmosis Membrane Biocide | NA |
| Formula 6025 | Reverse Osmosis Antiscalant | 30mg/L |
| Formula 6030 | Reverse Osmosis Antiscalant | 50mg/L |
| Formula 6035 | Reverse Osmosis Antiscalant | 25mg/L |
| Formula 6040 | Reverse Osmosis Antiscalant | 100mg/L |
| Formula 6042 | Reverse Osmosis Antiscalant | 50mg/L |
| Formula 6045 | Reverse Osmosis Antiscalant | 25mg/L |
| Formula 9033[4] | Membrane Cleaner | NA |
| Formula 9067[4] | Membrane Cleaner | NA |
| Formula 9098[4] [5] | Membrane Cleaner Pipe Cleaning Aid |
NA |
| Formula 9810[6] | Other | 50mg/L |
[3] This product is designed to be used off-line and flushed out prior to using the system
for drinking water, following manufacturer's use instructions.
The pH of the influent and effluent water should be monitored to ensure that all traces
of the product have been removed before placing into service.
Drain and flush system until the hydrogen peroxide and peracetic acid concentrations
fall below 1 ppm.
[4] This product is designed to be used off-line and flushed out prior to using the system
for drinking water, following manufacturer's use instructions.
The pH of the influent and effluent water should be monitored to ensure that all traces
of the product have been removed before placing into service.
[5] This product functions as an offline scale remover for the water distribution system,
parts, vessels and devices.
[6] This product is designed to reduce biofilms and help prevent the scaling and calcium
build-up on walls, piping systems and membrane surfaces of drinking water systems.
|
||
|
Poly (Diallyldimethylammonium Chloride)(pDADMAC) |
||
| Trade Designation | Product Function | Max Use |
| Formula 7633 | Coagulation & Flocculation | 25mg/L |
| Formula 7634 | Coagulation & Flocculation | 50mg/L |
| Formula 7642 | Coagulation & Flocculation | 50mg/L |
| Formula 7643 | Coagulation & Flocculation | 50mg/L |
|
Polyacrylamide[PC] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7187 | Coagulation & Flocculation | 1mg/L |
| Formula 7196 | Coagulation & Flocculation | 1mg/L |
| Formula 7273 | Coagulation & Flocculation | 1mg/L |
| Formula 7274 | Coagulation & Flocculation | 3mg/L |
| Formula 7278 | Coagulation & Flocculation | 1mg/L |
| Formula 7770 | Coagulation & Flocculation | 1mg/L |
| Formula 7882 | Coagulation & Flocculation | 1mg/L |
| Formula 7961 | Flocculant | 1mg/L |
[PC] Polyacrylamide Products Certified by NSF International comply with 40 CFR 141.111
requirements for percent monomer and dose.
|
||
|
Polyaluminum Chloride[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7062 | Coagulation & Flocculation | 250mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
|
||
|
Polyaluminum Chlorosulfate[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7066 | Coagulation & Flocculation | 450mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
|
||
|
Polyamines[PY] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7602 | Coagulation & Flocculation | 10mg/L |
| Formula 7603 | Coagulation & Flocculation | 10mg/L |
| Formula 7605 | Coagulation & Flocculation | 10mg/L |
| Formula 7622 | Coagulation & Flocculation | 10mg/L |
| Formula 7627 | Coagulation & Flocculation | 10mg/L |
| Formula 7655 | Coagulation & Flocculation | 10mg/L |
[PY] Polyamines Certified by NSF International comply with 40 CFR 141.111 requirements for
percent monomer and dose.
|
||
|
Polymer Blends[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7942[PY] | Coagulation & Flocculation | 200mg/L |
| Formula AH 423 | Coagulation & Flocculation | 100mg/L |
| Formula AH 710[PY] | Coagulation & Flocculation | 50mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
[PY] Polyamines Certified by NSF International comply with 40 CFR 141.111 requirements for
percent monomer and dose.
|
||
|
Sodium Bisulfite |
||
| Trade Designation | Product Function | Max Use |
| Formula 6600[7] | Dechlorination | 38mg/L |
[7] This product contains sulfite. Sulfites have been known to cause potentially lethal
allergic reactions in sulfite-sensitive individuals. The maximum recommended allowable
residual sulfite level in the finished drinking water is 100 ppb (0.1 mg/L).
|
||
|
Sodium Chlorite[8] [CL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 3000 | Chlorine Dioxide Production | 22mg/L |
| Formula 3007 | Chlorine Dioxide Production | 87mg/L |
[8] These products are certified for use in chlorine dioxide generation.
[CL] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations.
|
||
|
Sodium Hydroxide |
||
| Trade Designation | Product Function | Max Use |
| Formula LC | pH Adjustment | 100mg/L |
|
Sodium Hypochlorite[HY] |
||
| Trade Designation | Product Function | Max Use |
| Formula 305 | Disinfection & Oxidation | 35mg/L |
[HY] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations. Also,
reference the AWWA B300 (Hypochlorites) standard's Recommendations for the Handling and
Storage of Hypochlorite Solutions appendix for information on preservation techniques
for hypochlorite bleach in transit and storage.
|
||
|
Sodium Polyacrylate |
||
| Trade Designation | Product Function | Max Use |
| Formula 6050 | Reverse Osmosis Antiscalant | 50mg/L |
|
Sodium Silicate |
||
| Trade Designation | Product Function | Max Use |
| Formula 16 | Corrosion Control | 42mg/L |
| Formula 17 | Corrosion Control | 100mg/L |
|
Sodium Tripolyphosphate |
||
| Trade Designation | Product Function | Max Use |
| Formula 21-CC | Corrosion Control Sequestering |
12mg/L |
|
Tetrapotassium Pyrophosphate |
||
| Trade Designation | Product Function | Max Use |
| Formula 644 | Corrosion Control | 29mg/L |
Facility : Atlanta, GA
|
Aluminum Chlorohydrate[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7032 | Coagulation & Flocculation | 250mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
|
||
|
Blended Corrosion Inhibitor |
||
| Trade Designation | Product Function | Max Use |
| Formula 647 | Corrosion & Scale Control Sequestering |
27 mg/L |
|
Blended Phosphates |
||
| Trade Designation | Product Function | Max Use |
| Formula 6648 | Corrosion & Scale Control Sequestering |
50 mg/L |
|
Chlorine Dioxide, Liquid[CL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 3080 | Disinfection & Oxidation | 670mg/L |
[CL] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations.
|
||
|
Hydrochloric Acid[1] |
||
| Trade Designation | Product Function | Max Use |
| Formula 5300 | Other | 40mg/L |
| Formula 5307 | Other | 40mg/L |
[1] Certified for use as an activator for sodium chlorite in the generation of chlorine
dioxide.
|
||
|
Miscellaneous Corrosion Chemicals |
||
| Trade Designation | Product Function | Max Use |
| Formula 153 | Corrosion & Scale Control Sequestering |
50 mg/L |
|
Miscellaneous Treatment Chemical[2] |
||
| Trade Designation | Product Function | Max Use |
| Formula 65 | Antifoamer | 50mg/L |
[2] Certified for addition to the feedwater for evaporate desalination units only. |
||
|
Miscellaneous Water Supply Products |
||
| Trade Designation | Product Function | Max Use |
| Formula 3010[3] [4] [5] | Reverse Osmosis Membrane Biocide | NA |
| Formula 6025 | Reverse Osmosis Antiscalant | 30mg/L |
| Formula 6030 | Reverse Osmosis Antiscalant | 50mg/L |
| Formula 6035 | Reverse Osmosis Antiscalant | 25mg/L |
| Formula 6040 | Reverse Osmosis Antiscalant | 100mg/L |
| Formula 6042 | Reverse Osmosis Antiscalant | 50mg/L |
| Formula 6045 | Reverse Osmosis Antiscalant | 25mg/L |
| Formula 9033[4] [5] | Membrane Cleaner | NA |
| Formula 9067[4] [5] | Membrane Cleaner | NA |
| Formula 9098[4] [5] [6] | Membrane Cleaner Pipe Cleaning Aid |
NA |
| Formula 9810[7] | Other | 50mg/L |
[3] Drain and flush system until the hydrogen peroxide and peracetic acid concentrations
fall below 1 ppm.
[4] This product is designed to be used off-line and flushed out prior to using the system
for drinking water, following manufacturer's use instructions.
[5] The pH of the influent and effluent water should be monitored to ensure that all traces
of the product have been removed before placing into service.
[6] This product functions as an offline scale remover for the water distribution system,
parts, vessels and devices.
[7] This product is designed to reduce biofilms and help prevent the scaling and calcium
build-up on walls, piping systems and membrane surfaces of drinking water systems.
|
||
|
Poly (Diallyldimethylammonium Chloride)(pDADMAC) |
||
| Trade Designation | Product Function | Max Use |
| Formula 7633 | Coagulation & Flocculation | 25 mg/L |
| Formula 7642 | Coagulation & Flocculation | 50 mg/L |
|
Polyacrylamide[PC] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7187 | Coagulation & Flocculation | 1 mg/L |
| Formula 7274 | Coagulation & Flocculation | 3mg/L |
| Formula 7961 | Flocculant | 1mg/L |
[PC] Polyacrylamide Products Certified by NSF International comply with 40 CFR 141.111
requirements for percent monomer and dose.
|
||
|
Polyaluminum Chlorosulfate[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7066 | Coagulation & Flocculation | 450mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
|
||
|
Polyamines[PY] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7622 | Coagulation & Flocculation | 10 mg/L |
[PY] Polyamines Certified by NSF International comply with 40 CFR 141.111 requirements for
percent monomer and dose.
|
||
|
Polymer Blends |
||
| Trade Designation | Product Function | Max Use |
| Formula AH 423[AL] | Coagulation & Flocculation | 100mg/L |
| Formula AH 710[AL] [PY] | Coagulation & Flocculation | 50mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
[PY] Polyamines Certified by NSF International comply with 40 CFR 141.111 requirements for
percent monomer and dose.
|
||
|
Sodium Bisulfite |
||
| Trade Designation | Product Function | Max Use |
| Formula 6600[8] | Dechlorination | 38mg/L |
[8] This product contains sulfite. Sulfites have been known to cause potentially lethal
allergic reactions in sulfite-sensitive individuals. The maximum recommended allowable
residual sulfite level in the finished drinking water is 100 ppb (0.1 mg/L).
|
||
|
Sodium Chlorite[9] [CL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 3000 | Chlorine Dioxide Production | 22mg/L |
| Formula 3007 | Chlorine Dioxide Production | 87mg/L |
[9] These products are certified for use in chlorine dioxide generation.
[CL] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations.
|
||
|
Sodium Hydroxide |
||
| Trade Designation | Product Function | Max Use |
| Formula LC | pH Adjustment | 100mg/L |
|
Sodium Hypochlorite[HY] |
||
| Trade Designation | Product Function | Max Use |
| Formula 305 | Disinfection & Oxidation | 35mg/L |
[HY] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations. Also,
reference the AWWA B300 (Hypochlorites) standard's Recommendations for the Handling and
Storage of Hypochlorite Solutions appendix for information on preservation techniques
for hypochlorite bleach in transit and storage.
|
||
|
Sodium Polyacrylate |
||
| Trade Designation | Product Function | Max Use |
| Formula 6050 | Reverse Osmosis Antiscalant | 50mg/L |
|
Sodium Silicate |
||
| Trade Designation | Product Function | Max Use |
| Formula 16 | Corrosion & Scale Control | 42 mg/L |
| Formula 17 | Corrosion & Scale Control | 100 mg/L |
|
Sodium Tripolyphosphate |
||
| Trade Designation | Product Function | Max Use |
| Formula 21-CC | Corrosion Control Sequestering |
12 mg/L |
|
Tetrapotassium Pyrophosphate |
||
| Trade Designation | Product Function | Max Use |
| FORMULA 644 | Corrosion Control | 29 mg/L |
Facility : Addison, IL
|
Aluminum Chloride[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7032 | Coagulation & Flocculation | 250mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
|
||
|
Blended Corrosion Inhibitor |
||
| Trade Designation | Product Function | Max Use |
| Formula 647 | Corrosion & Scale Control Sequestering |
27 mg/L |
|
Blended Phosphates |
||
| Trade Designation | Product Function | Max Use |
| Formula 6648 | Corrosion & Scale Control Sequestering |
50 mg/L |
|
Chlorine Dioxide, Liquid[CL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 3080 | Disinfection & Oxidation | 670mg/L |
[CL] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations.
|
||
|
Hydrochloric Acid[1] |
||
| Trade Designation | Product Function | Max Use |
| Formula 5300 | Other | 40mg/L |
| Formula 5307 | Other | 40mg/L |
[1] Certified for use as an activator for sodium chlorite in the generation of chlorine
dioxide.
|
||
|
Miscellaneous Corrosion Chemicals |
||
| Trade Designation | Product Function | Max Use |
| Formula 153 | Corrosion & Scale Control Sequestering |
50 mg/L |
|
Miscellaneous Treatment Chemical[2] |
||
| Trade Designation | Product Function | Max Use |
| Formula 65 | Antifoamer | 50mg/L |
[2] Certified for addition to the feedwater for evaporate desalination units only. |
||
|
Miscellaneous Water Supply Products |
||
| Trade Designation | Product Function | Max Use |
| Formula 3010[3] [4] | Reverse Osmosis Membrane Biocide | NA |
| Formula 6025 | Reverse Osmosis Antiscalant | 30mg/L |
| Formula 6030 | Reverse Osmosis Antiscalant | 50mg/L |
| Formula 6035 | Reverse Osmosis Antiscalant | 25mg/L |
| Formula 6040 | Reverse Osmosis Antiscalant | 100mg/L |
| Formula 6042 | Reverse Osmosis Antiscalant | 50mg/L |
| Formula 6045 | Reverse Osmosis Antiscalant | 25mg/L |
| Formula 9033[4] [5] | Membrane Cleaner | NA |
| Formula 9067[4] [5] | Membrane Cleaner | NA |
| Formula 9098[4] [5] [6] | Membrane Cleaner Pipe Cleaning Aid |
NA |
| Formula 9810[7] | Other | 50mg/L |
[3] The pH of the influent and effluent water should be monitored to ensure that all traces
of the product have been removed before placing into service.
Drain and flush system until the hydrogen peroxide and peracetic acid concentrations
fall below 1 ppm.
[4] This product is designed to be used off-line and flushed out prior to using the system
for drinking water, following manufacturer's use instructions.
[5] The pH of the influent and effluent water should be monitored to ensure that all traces
of the product have been removed before placing into service.
[6] This product functions as an offline scale remover for the water distribution system,
parts, vessels and devices.
[7] This product is designed to reduce biofilms and help prevent the scaling and calcium
build-up on walls, piping systems and membrane surfaces of drinking water systems.
|
||
|
Poly (Diallyldimethylammonium Chloride)(pDADMAC) |
||
| Trade Designation | Product Function | Max Use |
| Formula 7633 | Coagulation & Flocculation | 25 mg/L |
| Formula 7634 | Coagulation & Flocculation | 50 mg/L |
| Formula 7642 | Coagulation & Flocculation | 50 mg/L |
| Formula 7643 | Coagulation & Flocculation | 50 mg/L |
|
Polyacrylamide[PC] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7187 | Coagulation & Flocculation | 1 mg/L |
| Formula 7196 | Coagulation & Flocculation | 1 mg/L |
| Formula 7273 | Coagulation & Flocculation | 1 mg/L |
| Formula 7274 | Coagulation & Flocculation | 3mg/L |
| Formula 7278 | Coagulation & Flocculation | 1 mg/L |
| Formula 7770 | Coagulation & Flocculation | 1 mg/L |
| Formula 7882 | Coagulation & Flocculation | 1 mg/L |
| Formula 7961 | Flocculant | 1mg/L |
[PC] Polyacrylamide Products Certified by NSF International comply with 40 CFR 141.111
requirements for percent monomer and dose.
|
||
|
Polyaluminum Chloride[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7062 | Coagulation & Flocculation | 250 mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
|
||
|
Polyaluminum Chlorosulfate[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7066 | Coagulation & Flocculation | 450mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
|
||
|
Polyamines[PY] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7602 | Coagulation & Flocculation | 10 mg/L |
| Formula 7603 | Coagulation & Flocculation | 10 mg/L |
| Formula 7605 | Coagulation & Flocculation | 10 mg/L |
| Formula 7622 | Coagulation & Flocculation | 10 mg/L |
| Formula 7627 | Coagulation & Flocculation | 10 mg/L |
| Formula 7655 | Coagulation & Flocculation | 10 mg/L |
[PY] Polyamines Certified by NSF International comply with 40 CFR 141.111 requirements for
percent monomer and dose.
|
||
|
Polymer Blends[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula AH 423 | Coagulation & Flocculation | 100 mg/L |
| Formula AH 710[PY] | Coagulation & Flocculation | 50 mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
[PY] Polyamines Certified by NSF International comply with 40 CFR 141.111 requirements for
percent monomer and dose.
|
||
|
Sodium Bisulfite |
||
| Trade Designation | Product Function | Max Use |
| Formula 6600[8] | Dechlorination | 38mg/L |
[8] This product contains sulfite. Sulfites have been known to cause potentially lethal
allergic reactions in sulfite-sensitive individuals. The maximum recommended allowable
residual sulfite level in the finished drinking water is 100 ppb (0.1 mg/L).
|
||
|
Sodium Chlorite[9] [CL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 3000 | Chlorine Dioxide Production | 22mg/L |
| Formula 3007 | Chlorine Dioxide Production | 87mg/L |
[9] These products are certified for use in chlorine dioxide generation.
[CL] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations.
|
||
|
Sodium Hydroxide |
||
| Trade Designation | Product Function | Max Use |
| Formula LC | pH Adjustment | 100mg/L |
|
Sodium Hypochlorite[CL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 305 | Disinfection & Oxidation | 35mg/L |
[CL] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations.
|
||
|
Sodium Polyacrylate |
||
| Trade Designation | Product Function | Max Use |
| Formula 6050 | Reverse Osmosis Antiscalant | 50mg/L |
|
Sodium Silicate |
||
| Trade Designation | Product Function | Max Use |
| Formula 16 | Corrosion & Scale Control | 42 mg/L |
| Formula 17 | Corrosion & Scale Control | 100 mg/L |
|
Sodium Tripolyphosphate |
||
| Trade Designation | Product Function | Max Use |
| Formula 21-CC | Corrosion & Scale Control Sequestering |
12 mg/L |
|
Tetrapotassium Pyrophosphate |
||
| Trade Designation | Product Function | Max Use |
| Formula 644 | Corrosion & Scale Control | 29 mg/L |
Facility : Farmers Branch, TX
|
Aluminum Chlorohydrate[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7032 | Coagulation & Flocculation | 250 mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
|
||
|
Blended Corrosion Inhibitor |
||
| Trade Designation | Product Function | Max Use |
| Formula 647 | Corrosion & Scale Control Sequestering |
27 mg/L |
|
Blended Phosphates |
||
| Trade Designation | Product Function | Max Use |
| Formula 6648 | Corrosion & Scale Control Sequestering |
50 mg/L |
|
Chlorine Dioxide, Liquid[CL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 3080 | Disinfection & Oxidation | 670mg/L |
[CL] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations.
|
||
|
Hydrochloric Acid[1] |
||
| Trade Designation | Product Function | Max Use |
| Formula 5300 | Other | 40mg/L |
| Formula 5307 | Other | 40mg/L |
[1] Certified for use as an activator for sodium chlorite in the generation of chlorine
dioxide.
|
||
|
Miscellaneous Corrosion Chemicals |
||
| Trade Designation | Product Function | Max Use |
| Formula 153 | Corrosion & Scale Control Sequestering |
50 mg/L |
|
Miscellaneous Treatment Chemical[2] |
||
| Trade Designation | Product Function | Max Use |
| Formula 65 | Antifoamer | 50mg/L |
[2] Certified for addition to the feedwater for evaporate desalination units only. |
||
|
Miscellaneous Water Supply Products |
||
| Trade Designation | Product Function | Max Use |
| Formula 3010[3] [4] | Reverse Osmosis Membrane Biocide | NA |
| Formula 6025 | Reverse Osmosis Antiscalant | 30mg/L |
| Formula 6030 | Reverse Osmosis Antiscalant | 50mg/L |
| Formula 6035 | Reverse Osmosis Antiscalant | 25mg/L |
| Formula 6040 | Reverse Osmosis Antiscalant | 100mg/L |
| Formula 6042 | Reverse Osmosis Antiscalant | 50mg/L |
| Formula 6045 | Reverse Osmosis Antiscalant | 25mg/L |
| Formula 9033[4] [5] | Membrane Cleaner | NA |
| Formula 9067[4] [5] | Membrane Cleaner | NA |
| Formula 9098[4] [5] [6] | Membrane Cleaner Pipe Cleaning Aid |
NA |
| Formula 9810[7] | Other | 50mg/L |
[3] The pH of the influent and effluent water should be monitored to ensure that all traces
of the product have been removed before placing into service.
Drain and flush system until the hydrogen peroxide and peracetic acid concentrations
fall below 1 ppm.
[4] This product is designed to be used off-line and flushed out prior to using the system
for drinking water, following manufacturer's use instructions.
[5] The pH of the influent and effluent water should be monitored to ensure that all traces
of the product have been removed before placing into service.
[6] This product functions as an offline scale remover for the water distribution system,
parts, vessels and devices.
[7] This product is designed to reduce biofilms and help prevent the scaling and calcium
build-up on walls, piping systems and membrane surfaces of drinking water systems.
|
||
|
Poly (Diallyldimethylammonium Chloride)(pDADMAC) |
||
| Trade Designation | Product Function | Max Use |
| Formula 7633 | Coagulation & Flocculation | 25 mg/L |
| Formula 7634 | Coagulation & Flocculation | 50 mg/L |
| Formula 7642 | Coagulation & Flocculation | 50 mg/L |
| Formula 7643 | Coagulation & Flocculation | 50 mg/L |
|
Polyacrylamide[PC] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7882 | Coagulation & Flocculation | 1 mg/L |
| Formula 7187 | Coagulation & Flocculation | 1 mg/L |
| Formula 7196 | Coagulation & Flocculation | 1 mg/L |
| Formula 7273 | Coagulation & Flocculation | 1 mg/L |
| Formula 7274 | Coagulation & Flocculation | 3mg/L |
| Formula 7278 | Coagulation & Flocculation | 1 mg/L |
| Formula 7770 | Coagulation & Flocculation | 1 mg/L |
| Formula 7961 | Flocculant | 1mg/L |
[PC] Polyacrylamide Products Certified by NSF International comply with 40 CFR 141.111
requirements for percent monomer and dose.
|
||
|
Polyaluminum Chloride[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7062 | Coagulation & Flocculation | 250 mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
|
||
|
Polyaluminum Chlorosulfate[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7066 | Coagulation & Flocculation | 450mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
|
||
|
Polyamines[PY] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7602 | Coagulation & Flocculation | 10 mg/L |
| Formula 7603 | Coagulation & Flocculation | 10 mg/L |
| Formula 7605 | Coagulation & Flocculation | 10 mg/L |
| Formula 7622 | Coagulation & Flocculation | 10 mg/L |
| Formula 7627 | Coagulation & Flocculation | 10 mg/L |
| Formula 7655 | Coagulation & Flocculation | 10 mg/L |
[PY] Polyamines Certified by NSF International comply with 40 CFR 141.111 requirements for
percent monomer and dose.
|
||
|
Polymer Blends[AL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 7942[PY] | Coagulation & Flocculation | 200mg/L |
| Formula AH 423 | Coagulation & Flocculation | 100 mg/L |
| Formula AH 710[PY] | Coagulation & Flocculation | 50 mg/L |
[AL] Based on an evaluation of health effects data, the level of aluminum in the finished
drinking water shall not exceed 2 mg/L.
[PY] Polyamines Certified by NSF International comply with 40 CFR 141.111 requirements for
percent monomer and dose.
|
||
|
Sodium Bisulfite |
||
| Trade Designation | Product Function | Max Use |
| Formula 6600[8] | Dechlorination | 38mg/L |
[8] This product contains sulfite. Sulfites have been known to cause potentially lethal
allergic reactions in sulfite-sensitive individuals. The maximum recommended allowable
residual sulfite level in the finished drinking water is 100 ppb (0.1 mg/L).
|
||
|
Sodium Chlorite[9] [CL] |
||
| Trade Designation | Product Function | Max Use |
| Formula 3000 | Chlorine Dioxide Production | 22mg/L |
| Formula 3007 | Chlorine Dioxide Production | 87mg/L |
[9] These products are certified for use in chlorine dioxide generation.
[CL] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations.
|
||
|
Sodium Hydroxide |
||
| Trade Designation | Product Function | Max Use |
| Formula LC | pH Adjustment | 100mg/L |
|
Sodium Hypochlorite[HY] |
||
| Trade Designation | Product Function | Max Use |
| Formula 305 | Disinfection & Oxidation | 35mg/L |
[HY] The residual levels of chlorine (hypochlorite ion and hypochlorous acid), chlorine
dioxide, chlorate ion, chloramine and disinfection by-products shall be monitored in the
finished drinking water to ensure compliance to all applicable regulations. Also,
reference the AWWA B300 (Hypochlorites) standard's Recommendations for the Handling and
Storage of Hypochlorite Solutions appendix for information on preservation techniques
for hypochlorite bleach in transit and storage.
|
||
|
Sodium Polyacrylate |
||
| Trade Designation | Product Function | Max Use |
| Formula 6050 | Reverse Osmosis Antiscalant | 50mg/L |
|
Sodium Silicate |
||
| Trade Designation | Product Function | Max Use |
| Formula 16 | Corrosion Control | 42 mg/L |
| Formula 17 | Corrosion Control | 100 mg/L |
|
Sodium Tripolyphosphate |
||
| Trade Designation | Product Function | Max Use |
| Formula 21-CC | Corrosion & Scale Control Sequestering |
12 mg/L |
|
Tetrapotassium Pyrophosphate |
||
| Trade Designation | Product Function | Max Use |
| Formula 644 | Corrosion & Scale Control | 29 mg/L |
Number of matching Manufacturers is 1