NSF Product and Service Listings
These NSF Official Listings are current as of Friday, December 26, 2025 at 12:15 a.m. Eastern Time. Please contact NSF to confirm the status of any Listing, report errors, or make suggestions.
Alert: NSF is concerned about fraudulent downloading and manipulation of website text. Always confirm this information by clicking on the below link for the most accurate information: http://info.nsf.org/Certified/PwsComponents/Listings.asp?Company=C0755801&Standard=061&
NSF/ANSI/CAN 61
Drinking Water System Components - Health Effects
Drinking Water System Components - Health Effects
NOTE: Unless otherwise indicated for Materials, Certification is only for the Water Contact Material shown in the Listing. Click here for a list of Abbreviations used in these Listings. Click here for the definitions of Water Contact Temperatures denoted in these Listings. Products certified to NSF/ANSI/CAN 61 comply with the health effects criteria in NSF/ANSI/CAN 600.
| Wanhua Chemical Group Co., Ltd. | |
| No. 59 Chongqing Street | |
| Yantai Econ. and Tech. Dev. Zone | |
| Yantai, Shandong 264006 | |
| China | |
| 86 535 202 6105 | |
| Visit this company's website |
Facility : Yantai, Shandong, China
Mechanical Devices
| Water | Water | |||
| Contact | Contact | |||
| Trade Designation | Size | Temp | Material | |
|
Reverse Osmosis Element |
||||
| BW-4040-FR[2] [4] | 4" x 40" | CLD 23 | MLTPL | |
| BW-4040-LP[2] [4] | 4" x 40" | CLD 23 | MLTPL | |
| BW-4040-ULP[2] [4] | 4" x 40" | CLD 23 | MLTPL | |
| BW-8040-400-FR[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| BW-8040-400-LP[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| BW-8040-400-ME[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| BW-8040-400-ULP[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| BW-8040-400-XFR[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| BW-8040-440-LP[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| BW-8040-440-ME[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| BW-8040-440-ULP[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| BW-8040-440-XLP[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| BW-FR[3] [5] | CLD 23 | MLTPL | ||
| BW-LP[3] [5] | CLD 23 | MLTPL | ||
| BW-ME[3] [5] | CLD 23 | MLTPL | ||
| BW-ULP[3] [5] | CLD 23 | MLTPL | ||
| BW-XFR[3] [5] | CLD 23 | MLTPL | ||
| BW-XLP[3] [5] | CLD 23 | MLTPL | ||
| HP200[3] [5] | CLD 23 | MLTPL | ||
| HP200-8040-270[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SCW-4040-ULP[2] [4] | 4" x 40" | CLD 23 | MLTPL | |
| SCW-8040-400-ULP[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SCW-8040-440-ULP[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SCW-ULP[3] [5] | CLD 23 | MLTPL | ||
| SW-4040-HF[2] [4] | 4" x 40" | CLD 23 | MLTPL | |
| SW-4040-HP70[2] [4] | 4" x 40" | CLD 23 | MLTPL | |
| SW-4040-HR[2] [4] | 4" x 40" | CLD 23 | MLTPL | |
| SW-4040-XHF[2] [4] | 4" x 40" | CLD 23 | MLTPL | |
| SW-4040-XHR[2] [4] | 4" x 40" | CLD 23 | MLTPL | |
| SW-8040-370-HP120[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SW-8040-400-HF[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SW-8040-400-HR[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SW-8040-400-XHF[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SW-8040-400-XHR[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SW-8040-440-HF[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SW-8040-440-HP70[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SW-8040-440-HR[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SW-8040-440-XHF[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SW-8040-440-XHR[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SW-8040-HP70[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| SW-HF[3] [5] | CLD 23 | MLTPL | ||
| SW-HP120[3] [5] | CLD 23 | MLTPL | ||
| SW-HP70[3] [5] | CLD 23 | MLTPL | ||
| SW-HR[3] [5] | CLD 23 | MLTPL | ||
| SW-XHF[3] [5] | CLD 23 | MLTPL | ||
| SW-XHR[3] [5] | CLD 23 | MLTPL | ||
| WH-400-PRO[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| WH-400-PRO1[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| WH-400-PRO2[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| WH-400-PRO3[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| WH-PRO[3] [5] | CLD 23 | MLTPL | ||
| WH-PRO1[3] [5] | CLD 23 | MLTPL | ||
| WH-PRO2[3] [5] | CLD 23 | MLTPL | ||
| WH-PRO3[3] [5] | CLD 23 | MLTPL | ||
| WNF5010[3] [5] | CLD 23 | MLTPL | ||
| WNF5010-8040-400[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| WNF5010-8040-440[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| WNF8010[3] [5] | CLD 23 | MLTPL | ||
| WNF8010-8040-400[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| WNF8020[3] [5] | CLD 23 | MLTPL | ||
| WNF8020-8040-400[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| WNF9010[3] [5] | CLD 23 | MLTPL | ||
| WNF9010-8040-370-P80[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| WNF9010-8040-400[2] [4] | 8" x 40" | CLD 23 | MLTPL | |
| WNF9010-P80[3] [5] | CLD 23 | MLTPL | ||
[2] Filter elements are certified for the following minimum daily (24 hour) permeate
generation volumes for use in public water treatment facilities:
BW-8040-400-LP: 9350 gallons
BW-8040-440-LP: 10285 gallons
BW-8040-400-FR: 9350 gallons
BW-8040-400-ULP: 9350 gallons
BW-8040-440-ULP: 10752 gallons
BW-8040-400-XFR: 9350 gallons
BW-8040-440-XLP: 10285 gallons
BW-8040-400-ME: 8925 gallons
BW-8040-440-ME: 9817 gallons
SW-8040-HP70: 7480 gallons
SW-8040-440-HP70: 8228 gallons
SW-8040-400-HR: 6375 gallons
SW-8040-440-HR: 7012 gallons
SW-8040-400-HF: 7650 gallons
SW-8040-440-HF: 8415 gallons
SW-8040-400-XHR: 5100 gallons
SW-8040-440-XHR: 5610 gallons
SW-8040-400-XHF: 6993 gallons
SW-8040-440-XHF: 8376 gallons
SW-8040-370-HP120: 10200 gallons
SCW-8040-400-ULP: 9350 gallons
SCW-8040-440-ULP: 10752 gallons
BW-4040-FR: 2400 gallons
BW-4040-LP: 2400 gallons
BW-4040-ULP: 2400 gallons
SCW-4040-ULP: 2400 gallons
SW-4040-HF: 1624 gallons
SW-4040-HP70: 1588 gallons
SW-4040-HR: 1353 gallons
SW-4040-XHF: 1485 gallons
SW-4040-XHR: 1083 gallons
WNF5010-8040-400: 10625 gallons
WNF5010-8040-440: 11687 gallons
WNF8010-8040-400: 11900 gallons
WNF8020-8040-400: 9350 gallons
WNF9010-8040-370-P80: 5440 gallons
WNF9010-8040-400: 6375 gallons
HP200-8040-270: 5780 gallons
WH-400-PRO: 9775 gallons
WH-400-PRO1: 9775 gallons
WH-400-PRO2: 9775 gallons
WH-400-PRO3: 9775 gallons
[3] Membranes are certified to a maximum static surface area to volume ratio of 0.13 liters
(L) per square meter of membrane surface area, and the following minimum daily (24 hour)
permeate generation volumes for use in public water treatment facilities:
BW-FR: 954 liters per square meter of membrane
BW-LP: 954 liters per square meter of membrane
BW-ME: 910 liters per square meter of membrane
BW-ULP: 954 liters per square meter of membrane
BW-XFR: 954 liters per square meter of membrane
BW-XLP: 954 liters per square meter of membrane
SCW-ULP: 954 liters per square meter of membrane
SW-HF: 780 liters per square meter of membrane
SW-HP70: 763 liters per square meter of membrane
SW-HP120: 1125 liters per square meter of membrane
SW-HR: 650 liters per square meter of membrane
SW-XHF: 713 liters per square meter of membrane
SW-XHR: 520 liters per square meter of membrane
WNF5010: 1084 liters square meter of membrane
WNF8010: 1214 liters square meter of membrane
WNF8020: 954 liters per square meter of membrane
WNF9010: 650 liters per square meter of membrane
WNF9010-P80: 600 liters per square meter of membrane
HP200: 873 liters per square meter of membrane
WH-PRO: 997 liters per square meter of membrane
WH-PRO1: 997 liters per square meter of membrane
WH-PRO2: 997 liters per square meter of membrane
WH-PRO3: 997 liters per square meter of membrane
[4] The following filter elements require a pre-service flush at a flow rate of 12 gallons
per minute (12 gpm) for 2 hours using deionized water:
BW-8040-400-LP
BW-8040-440-LP
BW-8040-400-FR
BW-8040-400-ULP
BW-8040-440-ULP
BW-8040-400-XFR
BW-8040-440-XLP
BW-8040-400-ME
BW-8040-440-ME
SW-8040-HP70
SW-8040-440-HP70
SW-8040-400-HR
SW-8040-440-HR
SW-8040-400-HF
SW-8040-440-HF
SW-8040-400-XHR
SW-8040-440-XHR
SW-8040-400-XHF
SW-8040-440-XHF
SW-8040-370-HP120
SCW-8040-400-ULP
SCW-8040-440-ULP
"BW-4040-FR
BW-4040-LP
BW-4040-ULP
SCW-4040-ULP
SW-4040-HF
SW-4040-HP70
SW-4040-HR
SW-4040-XHF
SW-4040-XHR
WNF5010-8040-400
WNF5010-8040-440
WNF8010-8040-400
WNF8020-8040-400
WNF9010-8040-370-P80
WNF9010-8040-400
HP200-8040-270
WH-400-PRO
WH-400-PRO1
WH-400-PRO2
WH-400-PRO3
[5] The following membranes require a pre-service immersion in ambient deionized water for
46 minutes, followed by a deonized water flush on both sides of the membrane for 30
minutes:
BW-FR
BW-LP
BW-ME
BW-ULP
BW-XFR
BW-XLP
SCW-ULP
SW-HF
SW-HP70
SW-HP120
SW-HR
SW-XHF
SW-XHR
WNF5010
WNF8010
WNF8020
WNF9010
WNF9010-P80"
HP200
WH-PRO
WH-PRO1
WH-PRO2
WH-PRO3
|
||||
|
Ultrafiltration Devices[1] |
||||
| UF-0685-50 | 160 x 2418 mm | CLD 23 | MLTPL | |
| UF-0685-65 | 160 x 2418 mm | CLD 23 | MLTPL | |
| UF-0770 | 180 x 1919 mm | CLD 23 | MLTPL | |
| UF-0860 | 225 x 1860 mm | CLD 23 | MLTPL | |
| UF-0880 | 225 x 2360 mm | CLD 23 | MLTPL | |
| UF-0880X | 225 x 2360 mm | CLD 23 | MLTPL | |
[1] Products require a pre-service flush at a flow rate of twelve (12) gallons per minute
(gpm) for two (2) hours using de-ionized water.
UF-0860 is certified for a minimum daily flow of 42,000 liters for use in public water
treatment facilities.
UF-0880 is certified for a minimum daily flow of 65,000 liters for use in public water
treatment facilities.
UF-0880X is certified for a minimum daily flow of 67,000 liters for use in public water
treatment facilities.
UF-0770 is certified for a minimum daily flow of 47,000 liters for use in public water
treatment facilities.
UF-0685-50 is certified for a minimum daily flow of 42,000 liters for use in public
water treatment facilities.
UF-0685-65 is certified for a minimum daily flow of 55,000 liters for use in public
water treatment facilities.
|
||||
Number of matching Manufacturers is 1
Number of matching Products is 71
Processing time was 0 seconds