NSF/ANSI 419
Public Drinking Water Equipment Performance - Filtration
Facility : Loves Park, IL
|
|
|
Microfiltration Devices[1]
|
|
Aqua MultiBore® C-Series |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.28 log, and a minimum LRV of 5.92 log. The maximum certified filtrate flux
rate is 400 gfd.
|
Facility : Hangzhou, Zhejiang, China
|
|
|
Ultrafiltration Devices
|
|
UNA-620A[1] |
|
UNA-620AB[1] |
|
UNA620A-DCA[2] |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.272 log, and a minimum LRV of 6.09 log. The maximum Certified filtrate flux
is 120 gfd.
[2] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.11 log, and a minimum LRV of 5.90 log. The maximum Certified filtrate flux is
60 gfd.
|
Facility : Fuji, Sizuoka, Japan
|
|
|
Ultrafiltration Devices[1]
|
|
UNA-620A |
|
UNA-620AB |
|
UNA620A-ADA |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.272 log, and a minimum LRV of 6.09 log. The maximum Certified filtrate flux
is 120 gfd.
|
Facility : Texas, USA
|
|
|
Ultrafiltration Devices
|
|
SiC BLOX FX series [1] |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 4.511 log, and a minimum LRV of 4.22 log. The maximum certified filtrate flux
rate is 249.9 gfd.
|
Facility : Lynge, Denmark
|
|
|
Ultrafiltration Devices
|
|
SiC BLOX FX series[1] |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 4.511 log, and a minimum LRV of 4.22 log. The maximum certified filtrate flux
rate is 249.9 gfd.
|
CERAFILTEC Germany GmbH | |
Quellenstr. 14 | |
Saarbrücken | |
66121 | |
Germany | |
49 681 93587 089 | |
Facility : Saarbruecken, Germany
|
|
|
Ultrafiltration Devices
|
|
CFT-0000-BMSEC4-2022[1] |
|
CFT-0000-SC0EC4-2022[1] |
|
CFT-0000-SMSEC4-2022[1] |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.21 log, and a minimum LRV of 5.64 log. The maximum certified filtrate flux
rate is 315.4 gfd.
|
DDP Specialty Electronic Materials US, Inc. | |
1803 Building | |
Midland, MI 48674 | |
United States | |
1-800-FILMTEC | |
989-638-6231 | |
Visit this company's website |
Facility : Zhejiang, China
|
|
|
Ultrafiltration Devices[1]
|
|
IntegraFlo™ IC52-XP |
|
IntegraFlux™SFD-2860XP |
|
IntegraFlux™SFD-2880XP |
|
IntegraFlux™UXA-2680XP |
|
IntegraPac™ IPD-51XP |
|
IntegraPac™ IPD-77XP |
|
IntegraTec™ XP 51 |
|
IntegraTec™ XP 51 IP |
|
IntegraTec™ XP 52 IC |
|
IntegraTec™ XP 55 UXA |
|
IntegraTec™ XP 55 UXA V |
|
IntegraTec™ XP 77 |
|
IntegraTec™ XP 77 IP |
|
UXA-2680XP |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.33 log, and a minimum LRV of 6.22 log. The maximum Certified filtrate flux is
70 gfd.
Also tested for virus reduction on 11/18/2020, with a mean LRV of 2.00 log, and a
minimum LRV of 1.85 log.
|
DuPont Memcor (Australia) Pty Ltd | |
15 Blackman Crescent | |
South Windsor, New South Wales 2756 | |
Australia | |
61 2 4577 0001 | |
Facility : Windsor, Australia
|
|
|
Ultrafiltration Devices
|
|
IntegraTec™ N 42 – L20N v2 / 120285[1] |
|
IntegraTec™ N 68 – L40N v2 / 120492[2] |
|
L10N Module / 120283[1] |
|
L40N Module /120309[2] |
|
S10N Module / 119221, 119222[1] |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.16 log, and a minimum LRV of 6.10 log. The maximum certified filtrate flux
rate is 155 gfd, which equals a flow rate of 32.5 gpm.
[2] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 5.71 log, and a minimum LRV of 3.48log. The maximum certified filtrate flux
rate is 85 gfd, which equals a flow rate of 42.6 gpm.
|
Facility : Oceanside, CA
|
|
|
Ultrafiltration Devices[1]
|
|
HYDRAcap® AM |
|
HYDRAcap® MAX 40 |
|
HYDRAcap® MAX 60 |
|
HYDRAcap® MAX 80 |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 5.81 log, and a minimum LRV of 5.54 log. The maximum certified filtrate flux
rate is 120 gfd.
|
Facility : Greifenberg, Germany
|
|
|
Ultrafiltration Devices[1]
|
|
dizzer® XL 0.9 MB 38 W |
|
dizzer® L 0.9 MB 40 PB |
|
dizzer® XL 0.9 MB 60 W |
|
dizzer™ XL 0.9 MB 60 WT |
|
dizzer™ XL 0.9 MB 70 WT |
|
dizzer® XL 0.9 MB 80 W |
|
dizzer® XL 0.9 MB 80 WT |
|
dizzer® XL 1.5 MB 40 W |
|
dizzer® XL 1.5 MB 50 WT |
|
dizzer P 2514-0.5 |
|
dizzer P 2521-1.0 |
|
dizzer P 4021-2.5 |
|
dizzer P 4040-6.0 |
|
IntegraTec™ MB 38 |
|
IntegraTec™ MB 40 |
|
IntegraTec™ MB 40 HB |
|
IntegraTec™ MB 50 TR |
|
IntegraTec™ MB 60 |
|
IntegraTec™ MB 80 |
|
IntegraTec™ MB 80 TR |
|
IntegraTec™ MB PRO 64 H |
|
IntegraTec™ MB PRO 95 |
|
IntegraTec™ MB PRO 95 TR |
|
TapTec™ P 2514-0.5 |
|
TapTec™ P 2521-1.0 |
|
TapTec™ P 4021-2.5 |
|
TapTec™ P 4040-6.0 |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
LRV) of 6.48 log, and a minimum LRV of 6.41 log. The maximum Certified filtrate flux is
106 gfd.
|
Meidensha Corporation | |
496-1 Ittangosewari | |
Nishibiwajima-cho, Kiyosu-shi | |
Aichi 452-8602 | |
Japan | |
81 52 509 1333 | |
Facility : Aichi, Japan
|
|
|
Ultrafiltration Devices[1]
|
|
CH250-1000E01K-5NA |
|
CH250-1000E02K-5NA |
|
CH250-1000E03K-5NA |
|
CH250-1000TM100-U1DJ-EKFPA0 |
|
CH250-1000TM100-U1DJ-ETLWA0 |
|
CH250-1000TM100-U2DJ-EKFPA0 |
|
CH250-1000TM100-U2DJ-ETLWA0 |
|
CH250-1000TM50-U1SJ-EKFPA0 |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.30 log, and a minimum LRV of 6.22 log. The maximum Certified filtrate flux is
176.40 gfd. Also, tested for virus removal efficiency with aluminum chlorohydrate
coagulant on May 3, 2021 at a maximum flux of 118.37 gfd, with a mean LRV of 5.50 log,
and a minimum LRV of 4.73 log. Tested for bacteria removal efficiency on November 10,
2015 at a maximum flux of 117.6 gfd, with a mean LRV of 5.93 log, and a minimum LRV of
5.48 log.
|
Facility : Hengelo, The Netherlands
|
|
|
Nanofiltration Devices
|
|
WMC200 dNF40[1] [2] |
|
WMC200 dNF80[1] [2] |
|
WRC200 IRD dNF40[1] [2] |
|
WRC200 IRD dNF80[1] [2] |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.26 log, and a minimum LRV of 5.56 log. The maximum Certified filtrate flux is
48 lmh.
[2] Tested for virus removal efficiency on FEB-08-2023 with a mean LRV of 6.26 log, and a
minimum LRV of 5.56 log.
|
Ultrafiltration Devices
|
|
WMC225 HYDRA cap™60[3] |
|
WMC225 HYDRA cap™60+[3] |
|
WMC225 HYDRA cap™60-LD[3] |
|
WMC225 HYDRA cap™60E[3] |
|
WMC225 HYDRA cap™60E+[3] |
[3] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.16 log, and a minimum LRV of 6.04 log. The maximum Certified filtrate flux
is 85 gfd.
|
Facility : Cortland, NY
|
|
|
Ultrafiltration Devices[1] [2]
|
|
Ultra60 MSA-620A |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.13 log, and a minimum LRV of 6.01 log. The maximum certified filtrate flux
rate is 120 gfd.
[2] Tested for virus removal efficiency on April, 13, 2022, with a mean LRV of 3.14 log, and
a minimum LRV of 2.08 log.
|
Facility : Beijing Scinor Membrane Technology Co., Ltd., China
|
|
|
Ultrafiltration Devices
|
|
SMT600-P38[1] |
|
SMT600-P50[2] |
|
SMT600-P51[2] |
|
SMT600-P52[2] |
|
SMT600-P53[2] |
|
SMT600-P55[2] |
|
SMT600-P56[2] |
|
SMT600-P57[2] |
|
SMT600-P60[2] |
|
SMT600-P72[2] |
|
SMT600-P80[2] |
|
SMT600-P81[2] |
|
SMT600-S26[3] |
|
SMT600-S40[3] |
|
SMT600-S48[3] |
|
SMT600-S51[3] |
|
SMT600-S60[3] |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.25 log, and a minimum LRV of 6.08 log. The maximum certified filtrate flux
rate is 120 gfd. Also tested 2/22/2016 for virus removal efficiency, with a mean LRV of
4.34 and a minimum LRV of 2.69 log.
[2] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.32 log, and a minimum LRV of 6.19 log. The maximum certified filtrate flux
rate is 120 gfd. Also tested 01/06/2021 for virus removal efficiency, with a mean LRV of
5.20 and a minimum LRV of 5.07 log.
[3] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.104 log, and a minimum LRV of 6.04 log. The
maximum certified filtrate flux rate is 120 gfd. Also tested on Dec. 22, 2021 for virus
removal efficiency with a mean LRV of 4.405 and a minimum LRV of 4.1 log.
|
Facility : Guangzhou, China
|
|
|
Ultrafiltration Devices
|
|
High Flow Series Filter HF-10-PP-0005-X-01[1] |
|
High Flow Series Filter HF-40-PP-0005-X-01[1] |
|
High Flow Series Filter HF-60-PP-0005-X-01[1] |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 2.58 log, and a minimum LRV of 2.25 log. The maximum certified filtrate flow
rate is 55 gpm.
|
Facility : F3
|
|
|
Ultrafiltration Devices[1]
|
|
HFU-2020AN |
|
HFUG-2020AN |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.28 log, and a minimum LRV of 5.20 log. Maximum Certified filtrate flow rate
is 244 LPM (64.6 GPM), and maximum Certified flux is 204 LMH (120 GFD). Also tested for
virus removal efficiency on December 4-5, 2018, with a mean LRV of 2.16 log, and a
minimum LRV of 1.67 log.
|
NOTE: If “F3” is indicated in the first two digits of the lot number, the facility location is
Suzhou, China.
Facility : F4
|
|
|
Ultrafiltration Devices
|
|
HFU-2020AN[1] |
|
HFU-B2315AN[2] |
|
HFUG-2020AN[1] |
|
HFUG-2020HN[1] |
|
HFUG-B2315AN[2] |
|
HFUG-L1720AN[1] |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.28 log, and a minimum LRV of 5.20 log. Maximum Certified filtrate flow rate
is 244 LPM (64.6 GPM), and maximum Certified flux is 204 LMH (120 GFD). Also tested for
virus removal efficiency on December 4-5, 2018, with a mean LRV of 2.16 log, and a
minimum LRV of 1.67 log.
[2] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.05 log, and a minimum LRV of 5.05 log. Maximum Certified filtrate flow rate
is 204 LPM (53.8 GPM), and maximum Certified flux is 204 LMH (120 GFD). Also tested for
virus removal efficiency on May 6-7, 2019, with a mean LRV of 1.39 log, and a minimum
LRV of 1.14 log.
|
NOTE: If “F4” is indicated in the first two digits of the lot number, the facility location is
Gyeongsangbuk-do, Korea.
Trojan Technologies | |
839 State Route 13 | |
Cortland, NY 13045 | |
United States | |
516-484-5400 | |
Facility : 1A
|
|
|
Ultrafiltration Devices
|
|
FLUXPRO 80 |
|
FLUXPRO 100 |
Facility : 2B
|
|
|
Ultrafiltration Devices
|
|
FLUXPRO 80 |
|
FLUXPRO 100 |
Facility : 3C
|
|
|
Ultrafiltration Devices
|
|
FLUXPRO 80 |
|
FLUXPRO 100 |
Trojan Technologies Corporation | |
839 State Route 13 | |
Cortland, NY 13045 | |
United States | |
866-475-0115 | |
Facility : Cortland, NY
|
|
|
Ultrafiltration Devices
|
|
Ultra60 MSA-620A[1] [2] |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.13 log, and a minimum LRV of 6.01 log. The maximum Certified filtrate flux
rate is 120 gfd.
[2] Tested for virus removal efficiency on April 13, 2022, with a mean LRV of 3.14 log, and
a minimum LRV of 2.08 log.
|
Veolia Water Technologies & Solutions | |
3600 Horizon Boulevard | |
Trevose, PA 19053 | |
United States | |
888-898-6766 | |
215-942-3534 | |
Facility : Oroszlány, Hungary
|
|
|
Ultrafiltration Devices
|
|
ZeeWeed 500d UF[1] |
[1] Certified by NSF for Cryptosporidium, with a mean log removal value (LRV) of 6.02 log
and a minimum LRV of 5.02 log. The maximum certified filtrate flux rate is 50 gfd,
which equals a flow rate of 15.3 gpm.
|
Facility : Zeewolde, The Netherlands
|
|
|
Ultrafiltration Devices[1]
|
|
ZW700B-10060 |
|
ZW700B-10072 |
|
ZW700B-4100 |
|
ZW700B-4150 |
|
ZW700B-450 |
|
ZW700B-6100 |
|
ZW700B-8060/X |
|
ZW700B-9060 |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.01 log, and a minimum LRV of 5.41 log. The maximum certified filtrate flux
rate is 100 gfd, which equals a flow rate of 29.9 gpm.
|
Wanhua Chemical Group Co., Ltd. | |
No. 59 Chongqing Street | |
Yantai Econ. and Tech. Dev. Zone | |
Yantai, Shandong 264006 | |
China | |
86 535 202 6105 | |
Visit this company's website |
Facility : Yantai, Shandong, China
|
|
|
Ultrafiltration Devices[1]
|
|
UF-0685-50 |
|
UF-0685-65 |
|
UF-0770 |
|
UF-0860 |
|
UF-0880 |
|
UF-0880X |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.36 log, and a minimum LRV of 5.64 log. The maximum certified filtrate flux
rate is 120 lmh.
|
X-Flow B.V. | |
Marssteden 50 | |
7547 Tc Enschede | |
The Netherlands | |
31-53 428 7350 | |
Facility : Enschede, The Netherlands
|
|
|
Nanofiltration Devices[1] [2]
|
|
HFW 1000 |
[1] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.04 log, and a minimum LRV of 4.71 log. The maximum certified filtrate flux
is 59.65 gfd.
[2] Also tested 6/20/2016 for virus removal efficiency, with a mean LRV of 5.54 and a
minimum LRV of 5.44 log.
|
Ultrafiltration Devices[3]
|
|
XF40 |
|
XF40C |
|
XF55 |
|
XF64 |
|
XF75 |
[3] Certified by NSF for Cryptosporidium removal efficiency, with a mean log removal value
(LRV) of 6.39 log, and a minimum LRV of 6.29 log. The maximum certified filtrate flux
is 73.5 gfd.
|
NSF Certification Guideline
Public Drinking Water Equipment Performance
NeoTech Aqua Solutions, Inc. | |
5893 Oberlin Drive | |
Suite 104 | |
San Diego, CA 92121 | |
United States | |
888-718-5040 | |
858-571-6590 | |
Visit this company's website |
Facility : San Diego, CA
|
|
|
Ultraviolet Reactor Devices[1]
|
|
NeoTech Aqua D438™ |
[1] Certified by NSF as achieving a minimum of 3-log inactivation of Cryptosporidium at
three conditions of sensor readings and flow rates (control set points). The three
control set points determined for a minimum 3-log inactivation of Cryptosporidium are
151 gpm - 7.9 mW/cm2; 251 gpm - 10.4 mW/cm2; and 501 gpm - 12.5 mW/cm2.
|
Number of matching Manufacturers is 20
Number of matching Products is 137
Processing time was 0 seconds